Choose a Destination:  Americas Asia & Pacific Europe Middle East & Africa

Maverick II Commercial Packaged Rooftop Systems
  • Overview
  • Specifications
  • Downloads

 

Heating/Cooling 15 to 75 Tons

 

Overview
System performance and reliability make Daikin McQuay Maverick II commercial packaged rooftop systems the ideal solution for new, retrofit or replacement applications on one to three-story buildings. Available in capacities from 15 to 70 tons, they combine the lower installation costs and interior space savings of a roof-mounted system with the operating and maintenance efficiencies of central heating and cooling systems.

Applications range from offices and schools to libraries and strip malls. Arriving at your job site as a complete package, Maverick II commercial rooftop systems maximize your design and installed cost savings. They also can add to your building’s profit margins year after year with efficient, reliable performance, and a wide array of features and benefits:

  • VAV or constant volume operation
  • Non-ozone depleting R-410A refrigerant
  • Optional energy heat recovery wheel for increased air conditioning capacity
  • Double wall construction protects insulation
  • Low leak damper meet ASHRAE standard 90.1
  • AF fans for efficient operation
  • Stainless steel drain pan for improved IAQ
  • Building pressure control option for exhaust fan
  • Controls flexibility—MicroTech®III controls with our Open Choices feature for easy integration with the BAS of your choice
  • Optional hot gas reheat for dehumidification control

 
 
Physical Data - 015 through 026

ModelMPS
015 ton017 ton020 ton026 ton
Cooling performance
Gross cooling capacity (tons)16.018.521.725.3
Nominal airflow (cfm)60007000800010,000
Maximum EER11.0 - 11.111.0 - 11.210.010.8
Maximum IEER11.2 - 11.511.2 - 12.011.212.8
Gas Heating Performance
Low heat MBH (input/output)1240/192240/192240/192240/192
Number of stages (low heat)2222
Turndown (low heat)24:14:14:14:1
Gas connection pipe size/qty (low heat)3/4"/13/4"/13/4"/13/4"/1
High heat MBH (input/output)1480/384480/384480/384480/384
Number of stages (high heat)4444
Gas connection pipe size/qty (high heat)3/4"/23/4"/23/4"/23/4"/2
Turndown (high heat)28:18:18:18:1
Steady state efficiency80%80%80%80%
Hot Water Heating Performance
Face area (sq ft)12.212.212.2512.25
Rows/FPI (low heat)1/111/111/141/14
Coil model (low heat)5WB5WB5WB5WB
Connection sizes/type (low heat)2ODM SweatODM SweatODM SweatODM Sweat
Rows/FPI (high heat)2/122/122/92/9
Coil model (high hea5WB5WB5WS5WS
Connection sizes/type (high heat)2ODM SweatODM SweatODM SweatODM Sweat
Electric Heating Performance
Number of stages4444
kW (low/medium/high heat)18/36/5418/36/5436/54/7236/54/72
Compressors
Type/numberScroll/2Scroll/2Scroll/2Scroll/2
Number of stages2244
Evaporator Coils
Rows4444
FPI14141313
Face area (sq ft)18.218.218.218.2
Capacity controlTxVTxVTxVTxV
Hot Gas Reheat
Coil typeMicrochannelMicrochannelMicrochannelMicrochannel
Control typeModulatingModulatingModulatingModulating
Face area (sq ft)14.114.114.114.1
Condenser Coils
Fin typeEnhancedEnhancedEnhancedEnhanced
FPI18181818
Face area (sq ft)18.118.118.118.1
Outdoor Fans
TypePropellerPropellerPropellerPropeller
Number - diameter2 - 26"2 - 26"2 - 26"2 - 26"
Drive type/number of speedsDirect/1Direct/1Direct/1Direct/1
Indoor Fans
TypeAF - SWSIAF - SWSIAF - SWSIAF - SWSI
Number - diameter1 - 18"1 - 18"1 - 20"1 - 22"
Drive typeFixed sheaveFixed sheaveFixed sheaveFixed sheave
Isolation1" spring1" spring1" spring1" spring
Number of motors1111
Motor hp range1.5 - 101.5 - 102 - 152 - 15
Motor nominal rpm1800180018001800
Motor efficiencyPremiumPremiumPremiumPremium
Filters
Type2", MERV 7
Area (sq ft)24242424
Qty. - size6 - 24" x 24"
Total Unit Weight
Weight (lbs)CoolingCoolingCoolingCooling
2650270029553055
Curb
Height14" - 24"14" - 24"14" - 24"14" - 24"
Weight (lbs)341 - 501341 - 501341 - 501341 - 501
  1. Piping connections are given with a male outside diameter dimension, brazed connection.
  2. Modulating burner only.
  3. Base unit weight includes Economizer, VFDs, and the smallest supply fan available. Heating units include maximum gas heat.

Physical Data - MPS 030 through 050

ModelMPS
030 ton035 ton040 ton050 ton
Cooling performance
Gross cooling capacity (tons)30.034.040.050.0
Nominal airflow (cfm)12,00014,00016,00020,000
Maximum EER10.2–10.49.9–10.110.0–10.39.8–10.2
Maximum IEER12.2–13.111.4–12.311.8–13.211.6–12.3
Gas Heating Performance
Low heat MBH (input/output)1300/240300/240400/320400/320
Number of stages (low heat)2222
Turndown (low heat)24:14:14:14:1
Gas connection pipe size/qty (low heat)3/4"/13/4"/13/4"/13/4"/1
High heat MBH (input/output)1600/480600/480800/640800/640
Number of stages (high heat)4444
Gas connection pipe size/qty (high heat)3/4"/23/4"/23/4"/23/4"/2
Turndown (high heat)28:18:18:18:1
Steady state efficiency80%80%80%80%
Hot Water Heating Performance
Face area (sq ft)19.2519.2519.2519.25
Rows/FPI (low heat)1/121/121/111/11
Coil model (low heat)5WB5WB5WH5WH
Connection sizes/type (low heat)2ODM SweatODM SweatODM SweatODM Sweat
Rows/FPI (high heat)2/102/102/132/13
Coil model (high hea5WS5WS5WS5WS
Connection sizes/type (high heat)2ODM SweatODM SweatODM SweatODM Sweat
Electric Heating Performance
Number of stages4444
kW (low/medium/high heat)54/72/9054/72/9072/90/10872/90/108
Compressors
Type/numberScroll/3Scroll/3Scroll/4Scroll/4
Number of stages5555
Evaporator Coils
Rows4444
FPI12121212
Face area (sq ft)25.425.429.435.7
Capacity controlTxVTxVTxVTxV
Hot Gas Reheat
Coil typeMicrochannelMicrochannelMicrochannelMicrochannel
Control typeModulatingModulatingModulatingModulating
Face area (sq ft)19.919.926.826.8
Condenser Coils
Fin typeEnhancedEnhancedEnhancedEnhanced
FPI18181818
Face area (sq ft)13.4/27.513.4/27.513.4/27.527.5 (× 2)
Outdoor Fans
TypePropellerPropellerPropellerPropeller
Number - diameter3 - 26"3 - 26"4 - 26"4 - 26"
Drive type/number of speedsDirect/1Direct/1Direct/1Direct/1
Indoor Fans
TypeAF - SWSIAF - SWSIAF - SWSIAF - SWSI
Number - diameter1 - 24"1 - 24"1 - 20"1 - 30"
Drive typeFixed sheaveFixed sheaveFixed sheaveFixed sheave
Isolation1" spring1" spring1" spring1" spring
Number of motors1111
Motor hp range5 - 205 - 207-1/2 - 307-1/2 - 30
Motor nominal rpm1800180018001800
Motor efficiencyPremiumPremiumPremiumPremium
Filters
Type2", MERV 6
Area (sq ft)32323644
Qty. - size8 - 24" × 24"8 - 24" × 24"8 – 24" × 24"/4 – 18" × 24"8 – 24" × 24"/4 – 18" × 24"
Total Unit Weight
Weight (lbs)CoolingCoolingCoolingCooling
3660366046854985
Curb
Height14" - 24"14" - 24"14" - 24"14" - 24"
Weight (lbs)341 - 501341 - 501481 - 501481 - 501
  1. Piping connections are given with a male outside diameter dimension, brazed connection.
  2. Modulating burner only.
  3. Base unit weight includes Economizer, VFDs, and the smallest supply fan available. Heating units include maximum gas heat.

Physical Data - MPS 062 through 075 

ModelMPS
062 ton070 ton075 ton
Cooling performance
Nominal gross cooling capacity (tons)62.070.075.0
Nominal airflow (cfm)24,00026,00028,000
Maximum EER10.0 - 10.39.79.3
Maximum IEER12.4 - 12.713.0 - 13.612.2 - 12.9
Gas Heating Performance
Low heat MBH (input/output)1500/400500/400500/400
Gas connection pipe size/qty (low heat)1"/11"/11"/1
Medium heat MBH (input/output)1600/480600/480800/640
Gas connection pipe size/qty (medium heat)1 1/4"/11 1/4"/11 1/4"/1
High heat MBH (input/output)1980/790980/790980/790
Gas connection pipe size/qty (high heat)1 1/4"/11 1/4"/11 1/4"/1
Number of stages - all furnaces (high heat)ModModMod
Turndown (high heat)23:13:18:1
Steady state efficiency80%80%80%
Hot Water Heating Performance
Face area (sq ft)29.729.729.7
Type - rows (standard / high capacity)5WH - 1 / 5WS - 25WH - 1 / 5WS - 25WH - 1 / 5WS - 2
FPI999
Electric Heating Performance
Number of stages444
kW (low/medium/high heat)100/120/160100/120/160100/120/160
Compressors
Type/numberScroll/4Scroll/6Scroll/6
Number of stages466
Evaporator Coils
Rows555
FPI101010
Face area (sq ft)39.5 or 47.147.147.1
Capacity controlTxVTxVTxV
Outdoor Fans
TypePropellerPropellerPropeller
Number - diameter6 - 26"6 - 26"6 - 26"
Drive type/number of speedsDirect/1Direct/1Direct/1
Indoor Fans
SWSI AFAF - SWSI
DWDI AF1 - 24"
Drive typeFixed sheave
Isolation2" spring
Number of motors1
Motor hp range5 - 20
Motor nominal rpm1800
Motor efficiencyPremium
Filters
Qty. - type / sq. ft.(7) 16 x 20 and (21) 16 x 25 / 73 sq. ft.
Area (sq ft)

Merv 6 angular:
(4) 12 x 24 and (8) 24 x 24 / 40 sq. ft. standard air flow

6" Merv 11 or 12" Merv 14:
(8) 12 x 24 and (8) 24 x 24 / 48 sq. ft. high air flow

  1. Heating output is for standard conditions at sea level.
  2. Modulating burner only.

 

Application Software
Brochures
Case Studies
Catalogs
Control Integration
Installation and Operation Manuals
Physical Data
Replacement Parts Lists
   Click here to view the Replacement Parts Model Index
Revit (BIM) Files
  • Unit  Maverick (Revit 2010 Zip) - (14.7MB) (Pub: 2012/03/12)
     
    Models:MPS
     
    Revit 2010 content for commercial packaged rooftop model MPS, Maverick I and Maverick II R-410A units. Maverick I units are 3 - 25 ton. Maverick II units are 15 - 50 ton.