Choose a Destination:  Americas Asia & Pacific Europe Middle East & Africa

Enfinity™ Model VFC/VFW Vertical Floor-mounted Water Source Heat Pumps

We are pleased to introduce the new Enfinity™ Model VFC/VFW vertical floor-mounted water source heat pump (sizes 009 thru 070).

Enfinity™ Model VFC/VFW vertical floor-mounted water source heat pumps use non-ozone depleting R-410A refrigerant, which – along with high Energy Efficiency Ratios (EER’s) – helps preserve our environment and precious energy resources.  Units offer maximum flexibility to help you achieve high efficiency, low operating costs and superior IAQ within your commercial or residential building budget.

Product Brochure                                  Complete Catalog

  • They can be selected for standard boiler/tower or geothermal applications
  • Multiple configurations reduce design time and help you avoid obstructions and use minimum ductwork to reduce installation costs
  • Multiple factory-installed features and options allow you to select the unit that closely matches your application requirements while lowering installation costs.
  • Small footprint design makes it easier to meet space requirements for new construction and replacement applications

Factory-installed Features and Options

  • R-410A Refrigerant – Has no ozone depletion potential or phase-out date, helping to minimize environmental impact and protect against refrigerant availability issues over the economic life of your equipment investment.
  • MicroTech® III Unit Controller – Open ChoicesTM control feature allows Standalone or easy integration into a LONWORKS® (LonMark 3.4 Certified) or BACnet® communications network using and add-on communication module.
  • ECM fan motor – improves unit efficiency and maintains constant airflow over varying system static pressure.
  • Hot Gas Reheat Coil – Required for many applications needing added humidity control, this option is selectable for sizes 019 to 070.
  • Desuperheater – this heat exchanger system aids in domestic hot water production while the water source heat pump is in the cooling mode of operation. 
  • Auxiliary/Emergency Electric Heat Coil (5kw or 10kw – single point power) – in emergency situations where the compressor no longer functions, the integral electric heat coil can provide temporary heating until the compressor is replaced.
  • 2-way motorized valves (NO or NC) – ideal for variable pumping applications – when there isn’t a call for unit operation, the valve closes, reducing the flow requirements through the condenser water loop.
  • Compressor Sound Blanket – new and improved compressor sound blanket for sound sensitive applications.
  • Painted Cabinet  - suitable for residential applications.

Performance Summary

Unit Size

Capacity (BTUH)

EER – Water Loop

EER – Ground Loop

EER – Ground Source

Nominal Airflow (CFM)

PSC

ECM

PSC

ECM

PSC

ECM

VFC007

*

*

N/A

*

N/A

*

N/A

*

VFC009

9,060

14.0

N/A

16.7

N/A

23.8

N/A

300

VFC012

12,000

14.4

N/A

16.9

N/A

23.8

N/A

400

VFC015

14,700

16.0

*

19.6

*

28.1

*

500

VFC019

19,200

15.2

16.6

17.3

19.0

23.5

26.1

600

VFC024

23,800

15.1

16.3

17.7

19.2

23.3

25.8

800

VFC030

30,000

17.0

17.0

19.1

19.3

25.1

25.5

1000

VFC036

39,500

14.8

15.0

17.3

16.6

22.3

21.3

1300

VFC042

43,900

15.0

16.2

17.0

18.9

22.1

24.8

1400

VFC048

48,100

14.7

16.0

15.8

18.2

20.3

23.8

1600

VFC060

63,200

15.1

15.7

16.3

18.0

20.5

22.9

2000

VFC070

75,400

13.5

14.0

13.7

16.2

16.6

19.6

2160

 
N/A = Not available