Latest News:
2009/12/08 Daikin McQuay Pathfinder Chiller Now Available with Optional VFD!2009/10/13 Daikin McQuay Magnitude™ Frictionless Centrifugal Chillers Now in 400 to 550 Tons!
2009/06/29 New Daikin McQuay Pathfinder™ air-cooled chiller helps reduce energy costs, meet sustainable goals.
2009/02/17 New McQuay Extended-Size Vision™ Indoor Air Handlers
2008/11/20 New Scroll Templifier™ Water Heater
2008/11/20 McQuay Equipment Quiet Enough for “On Air”
2008/04/09 The International Mechanical Code and ANSI/ASHRAE Standard 62.1-2004
Enfinity™ Model VFC/VFW Vertical Floor-mounted Water Source Heat Pumps
We are pleased to introduce the new Enfinity™ Model VFC/VFW vertical floor-mounted water source heat pump (sizes 009 thru 070). Enfinity™ Model VFC/VFW vertical floor-mounted water source heat pumps use non-ozone depleting R-410A refrigerant, which – along with high Energy Efficiency Ratios (EER’s) – helps preserve our environment and precious energy resources. Units offer maximum flexibility to help you achieve high efficiency, low operating costs and superior IAQ within your commercial or residential building budget. |
|
- They can be selected for standard boiler/tower or geothermal applications
- Multiple configurations reduce design time and help you avoid obstructions and use minimum ductwork to reduce installation costs
- Multiple factory-installed features and options allow you to select the unit that closely matches your application requirements while lowering installation costs.
- Small footprint design makes it easier to meet space requirements for new construction and replacement applications
Factory-installed Features and Options
- R-410A Refrigerant – Has no ozone depletion potential or phase-out date, helping to minimize environmental impact and protect against refrigerant availability issues over the economic life of your equipment investment.
- MicroTech® III Unit Controller – Open ChoicesTM control feature allows Standalone or easy integration into a LONWORKS® (LonMark 3.4 Certified) or BACnet® communications network using and add-on communication module.
- ECM fan motor – improves unit efficiency and maintains constant airflow over varying system static pressure.
- Hot Gas Reheat Coil – Required for many applications needing added humidity control, this option is selectable for sizes 019 to 070.
- Desuperheater – this heat exchanger system aids in domestic hot water production while the water source heat pump is in the cooling mode of operation.
- Auxiliary/Emergency Electric Heat Coil (5kw or 10kw – single point power) – in emergency situations where the compressor no longer functions, the integral electric heat coil can provide temporary heating until the compressor is replaced.
- 2-way motorized valves (NO or NC) – ideal for variable pumping applications – when there isn’t a call for unit operation, the valve closes, reducing the flow requirements through the condenser water loop.
- Compressor Sound Blanket – new and improved compressor sound blanket for sound sensitive applications.
- Painted Cabinet - suitable for residential applications.
Performance Summary
Unit Size | Capacity (BTUH) | EER – Water Loop | EER – Ground Loop | EER – Ground Source | Nominal Airflow (CFM) | |||
PSC | ECM | PSC | ECM | PSC | ECM | |||
VFC007 | * | * | N/A | * | N/A | * | N/A | * |
VFC009 | 9,060 | 14.0 | N/A | 16.7 | N/A | 23.8 | N/A | 300 |
VFC012 | 12,000 | 14.4 | N/A | 16.9 | N/A | 23.8 | N/A | 400 |
VFC015 | 14,700 | 16.0 | * | 19.6 | * | 28.1 | * | 500 |
VFC019 | 19,200 | 15.2 | 16.6 | 17.3 | 19.0 | 23.5 | 26.1 | 600 |
VFC024 | 23,800 | 15.1 | 16.3 | 17.7 | 19.2 | 23.3 | 25.8 | 800 |
VFC030 | 30,000 | 17.0 | 17.0 | 19.1 | 19.3 | 25.1 | 25.5 | 1000 |
VFC036 | 39,500 | 14.8 | 15.0 | 17.3 | 16.6 | 22.3 | 21.3 | 1300 |
VFC042 | 43,900 | 15.0 | 16.2 | 17.0 | 18.9 | 22.1 | 24.8 | 1400 |
VFC048 | 48,100 | 14.7 | 16.0 | 15.8 | 18.2 | 20.3 | 23.8 | 1600 |
VFC060 | 63,200 | 15.1 | 15.7 | 16.3 | 18.0 | 20.5 | 22.9 | 2000 |
VFC070 | 75,400 | 13.5 | 14.0 | 13.7 | 16.2 | 16.6 | 19.6 | 2160 |