Choose a Destination:  Americas Asia & Pacific Europe Middle East & Africa

RoofPak Applied Rooftop Systems
  • Overview
  • Specifications
  • Downloads

Air Cooled Condenser Arrangements

15 to 140 Tons (R-410A) 

Evaporative Condenser
Arrangements

75 to 150 tons

A Buildings Magazine
Top 100 Product for 2008

 

 

 

 

  
Complete Catalog: Air-Cooled Condenser Arrangments (pdf) - 8,331KB

Complete Catalog Evaporative Condenser Arrangements (pdf) - 3,388KB 

  • Now with R-410A refrigerant and ASHRAE 90.1 2010 efficiencies!
    Click here for more information. 
  • Modular construction
  • 100% make-up air, dehumidification, VAV, or constant volume operation
  • Multiple factory-integrated options for customized flexibility
  • Blow-through or draw-through cooling coil configurations
  • Controls flexibility—MicroTech II controls with our Open Choices™ feature for reduced installation cost and easy, low cost integration with the BAS of your choice
  • Heavy duty construction and independent certification (optional) confirm
    the McQuay RoofPak complies with the newest IBC seismic requirements
  • Evaporative systems provide up to 40% savings in condensing unit energy consumption versus air-cooled alternatives (available with chemical-free water treatment system)

 

Physical Data - 015 through 042

DataUnit Size
015D/016D020D/021D025D/026D030D/031D035D042D
Compressor
Quantity–hp2–71–100, 2–4.51–11.5, 2–5.5

1–13,
2–6

4–7.54–8.5
Capacity control100-50-0100-78-22-0100-78-22-0100-78-22-0100-75-50-25-0100-75-50-25-0
Condenser fans
Qty–diameter (in)2–262–262–264–264–264–26
Condenser fan motors
Qty–hp2–1.02–1.02–1.04–1.04–1.04–1.0
Supply fans
TypeForward curved LPForward curved LP/MP
Qty–diameter (in)2–15×6,
2–15×15
2–15×6,
2–15×15
2–15×6,
2–15×15
2–15×6,
2–15×15
1–241–24
Airflow range (cfm)4000–120004000–120005400–160005400–160005400–175505400–17550
Motor hp range1–201–201–201–201–251–25
TypeDWDI airfoil
Qty–diameter (in)1–201–201–201–201–241–24
Airflow range (cfm)4000–100004000–120005400–160005400–160005400–175505400–17550
Motor hp range1–201–201–201–201–251–24
Return fans
TypeForward curved
Qty–diameter (in)2–15×152–15×152–15×152–15×15
Airflow range (cfm)4000–100004000–120005400–160005400–16000
Motor hp range1–101–101–101–10
TypeSWSI airfoil
Qty–diameter (in)1–301–301–301–301–30,
1–40
1–30,
1–40
Airflow range (cfm)4000–100004000–120005400–160005400–160005400–175505400–17550
Motor hp range1–101–101–101–101–101–10
Evaporator coils
Rows4, 54, 54, 54, 54, 54, 5
FPI10, 1210, 1210, 1210, 1210, 1210, 12
Face area, small (sq ft)18.518.527.027.027.027.0
Hot water coils
Type–rows5WH–1,
5WS–2
5WH–1,
5WS–2
5WH–1,
5WS–2
5WH–1,
5WS–2
5WH–1,
5WS–2
5WH–1,
5WS–2
FPI999999
Face area (sq ft)20.320.320.320.320.320.3
Steam coils
Type–rows5JA–15JA–15JA–15JA–15JA–15JA–1
FPI6, 126, 126, 126, 126, 126, 12
Face area (sq ft)20.320.320.320.320.320.3
Gas furnace
Input (MBh)250, 312, 400, 500, 625, 800, 812, 988, 1000, 1250
Nominal output (MBh)200, 250, 320, 400, 500, 640, 650, 790, 800, 1000
Electric heat
Nominal output (kW)20, 40, 60, 80, 100, 120, 140, 160, 180, 200, 220, 240
Panel filters
Type85% (MERV 13) or 30% (MERV 7 or 8), pleated
Area (sq ft)50.050.050.050.050.050.0
Qty–size (in)10–16×20×2, 10–16×25×2
Prefilters (for cartridge filters)
TypePrefilter, 30% (MERV 7 or 8), standard flow
Area (sq ft)24.024.024.024.024.024.0
Qty–size (in)4–24×24×2, 4–12×24×2
Cartridge filters
Type65% (MERV 11) or 95% (MERV 14), standard flow
Area (sq ft)24.024.024.024.024.024.0
Qty–size (in)4–24×24×12, 4–12×24×12

NOTE:
1. Gas furnace size availability is limited by minimum airflow.
2. 460-volt capacities are shown. Electric heat availability is limited by minimum airflow.

 

Physical Data - 045 through 079

DataUnit Size
045D050D/051D062D/063D068D070D/071D075D/079D
Compressor
Quantity–hp4–104–11.54–13

4–15

6–106–11.5
3–11.5
Capacity control100-75-50-25-0100-83-67-50-33-17-0
Condenser fans
Qty–diameter (in)4–264–266–266–266–268–26
Condenser fan motors
Qty–hp4–1.04–1.06–1.06–1.06–1.08–1.0
RPS supply fans
TypeForward curved LP/MP
Qty–diameter (in)1– 271– 271– 271– 271– 278–26
Motor hp range3–503–503–503–503–508–1.0
TypeDWDI airfoil
Qty–diameter (in)1–27,301–27,301–30, 331–30, 331–30, 338–26
Motor hp range3–503–503–503–503–508–1.0
RDT supply fans
TypeSWSI airfoil
Qty–diameter (in)1–40,441–40,441–40,441–40,441–40,448–26
Motor hp range3–503–503–503–503–508–1.0
Return fans
TypeSWSI airfoil
Qty–diameter (in)1–401–401–401–401–401–40
Motor hp range2–302–302–302–302–302–30
Exhaust fans
TypePropeller
Diameter (in)363636363636
Qty.1 or 2 per unit
Motor hp range5 each5 each5 each5 each5 each5 each
Evaporator coils
Rows4, 54, 54, 54, 54, 54, 5
FPI10, 1210, 1210, 1210, 1210, 1210, 12
Face area, small (sq ft)39.539.539.539.539.539.5
Face area, large (sq ft)47.147.147.147.147.147.1
Hot water coils
Type–rows5WH–1,
5WS–2
5WH–1,
5WS–2
5WH–1,
5WS–2
5WH–1,
5WS–2
5WH–1,
5WS–2
5WH–1,
5WS–2
FPI999999
Face area (sq ft)29.729.729.729.729.729.7
Steam coils
Type–rows5JA–1, 25JA–1, 25JA–1, 25JA–1, 25JA–1, 25JA–1, 2
FPI6, 126, 126, 126, 126, 126, 12
Face area (sq ft)29.729.729.729.729.729.7
Gas furnace
Input (MBh)250, 312, 400, 500, 625, 800, 812, 988, 1000, 1250
Nominal output (MBh)200, 250, 320, 400, 500, 640, 650, 790, 800, 1000
Electric heat
Nominal output (kW)40, 60, 80, 100, 120, 160, 200, 240
Panel filters
Type85% (MERV 13) or 30% (MERV 7 or 8), pleated
Area (sq ft)73.973.973.973.973.973.9
Qty–size (in)7–16×20×2, 21–16×25×2
Prefilters (for cartridge filters)
TypePrefilter, 30% (MERV 7 or 8), standard flow
Area (sq ft)40.040.040.040.040.040.0
Qty–size (in)4–12×24×2, 8–24×24×2
TypePrefilter, 30% (MERV 7 or 8), standard flow
Area (sq ft)48.048.048.048.048.048.0
Qty–size (in)8–12×24×2, 8–24×24×2
Cartridge filters
Type65% (MERV 11) or 95% (MERV 14), standard flow
Area (sq ft)40.040.040.040.040.040.0
Qty–size (in)4–12×24×12, 8–24×24×12
Type65% (MERV 11) or 95% (MERV 14), standard flow
Area (sq ft)48.048.048.048.048.048.0
Qty–size (in)8–12×24×12, 8–24×24×12

NOTE:
1. Gas furnace size availability is limited by minimum airflow (RFS/RPS only).
2. 460-volt capacities are shown. Electric heat availability is limited by minimum airflow (RFS/RPS only).

 

Physical Data - 080 through 105

DataUnit Size
080D/081D085D090D/091D100D/101D105D
Compressor
Quantity–hp6–11.56–266–13

3–13
3–15

6–15
Capacity control100-83-67-50-33-17-0100-83-67-49-33-16-0100-84-67-50-33-17-0
Condenser fans
Qty–diameter (in)6–266–268–269–268–26
Condenser fan motors
Qty–hp6–1.06–1.08–1.09–1.08–1.0
Supply fans
TypeDWDI airfoil
Qty–diameter (in)1–33, 361–33, 361–33, 361–36, 401–36, 40
Motor hp range5–755–755–755–755–75
Return fans
TypeSWSI airfoil
Qty–diameter (in)1–44.51–44.51–44.51–44.51–44.5
Motor hp range5–605–605–605–605–60
Exhaust fans
TypePropeller
Diameter (in)3636363636
Qty1–3 per unit1–3 per unit1–3 per unit1–3 per unit1–3 per unit
Motor hp5 each5 each5 each5 each5 each
Evaporator coils
Rows4, 54, 54, 54, 54, 5
FPI10, 1210, 1210, 1210, 1210, 12
Face area, small (sq ft)53.953.953.960.860.8
Face area, large (sq ft)60.860.860.876.076.0
Hot water coils
Type–rows5WH–1,
5WS–2
5WH–1,
5WS–2
5WH–1,
5WS–2
5WH–1,
5WS–2
5WH–1,
5WS–2
FPI99999
Face area (sq ft)42.242.242.242.242.2
Steam coils
Type–rows5JA–1, 25JA–1, 25JA–1, 25JA–1, 25JA–1, 2
FPI6, 126, 126, 126, 126, 12
Face area (sq ft)42.242.242.242.242.2
Gas furnace
Input (MBh)625, 800, 812, 988, 1000, 1250, 1375, 1750, 1875, 2500
Nominal output (MBh)500, 640, 650, 790, 800, 1000, 1100, 1400, 1500, 2000
Electric heat
Nominal output (kW)80, 100, 120, 160, 200, 240, 280, 320
Panel filters
Type85% (MERV 13) or 30% (MERV 7 or 8), pleated
Area (sq ft)116.1116.1116.1116.1116.1
Qty–size (in)11–16×20×2, 33–16×25×2
Prefilters (for cartridge filters)
TypePrefilter, 30% (MERV 7 or 8), standard flow
Area (sq ft)56.056.056.056.056.0
Qty–size (in)4–12×24×2, 12–24×24×216–24×24×2
TypePrefilter, 30% (MERV 7 or 8), standard flow
Area (sq ft)64.064.064.064.064.0
Qty–size (in)16–24×24×28–12×24×2, 16–24×24×2
Cartridge filters
Type65% (MERV 11) or 95% (MERV 14), standard flow
Area (sq ft)56.056.056.056.056.0
Qty–size (in)4–12×24×12, 12–24×24×1216–24×24×12
Type65% (MERV 11) or 95% (MERV 14), standard flow
Area (sq ft)64.064.064.064.064.0
Qty–size (in)16–24×24×128–12×24×12
16–24×24×12

NOTE:
1. Gas furnace size availability is limited by minimum airflow (RFS/RPS only).
2. 460-volt capacities are shown. Electric heat availability is limited by minimum airflow (RFS/RPS only).

 

Physical Data - 080 through 140

DataUnit Size
110D120D125D130D140D
Compressor
Quantity–hp6–153–15
3–20
6–20

6–20

3–20
3–25
Capacity control100-84-67-50-33-17-0100-83-67-49-33-16-0100-84-67-50-33-17-0100-83-67-49-33-16-0
Condenser fans
Qty–diameter (in)8–269–2610–2612–2612–26
Condenser fan motors
Qty–hp8–1.09–1.010–1.012–1.012–1.0
Supply fans
TypeDWDI airfoil
Qty–diameter (in)1–36, 401–36, 401–36, 401–36, 401–36, 40
Motor hp range5–755–755–755–755–75
Return fans
TypeSWSI airfoil
Qty–diameter (in)1–44.51–44.51–44.51–44.51–44.5
Motor hp range5–605–605–605–605–60
Exhaust fans
TypePropeller
Diameter (in)3636363636
Qty1–3 per unit1–3 per unit1–3 per unit1–3 per unit1–3 per unit
Motor hp5 each5 each5 each5 each5 each
Evaporator coils
Rows4, 54, 54, 54, 54, 5
FPI10, 1210, 1210, 1210, 1210, 12
Face area, small (sq ft)60.860.8
Face area, large (sq ft)76.076.076.076.076.0
Hot water coils
Type–rows5WH–1,
5WS–2
5WH–1,
5WS–2
5WH–1,
5WS–2
5WH–1,
5WS–2
5WH–1,
5WS–2
FPI99999
Face area (sq ft)42.242.242.242.242.2
Steam coils
Type–rows5JA–1, 25JA–1, 25JA–1, 25JA–1, 25JA–1, 2
FPI6, 126, 126, 126, 126, 12
Face area (sq ft)42.242.242.242.242.2
Gas furnace
Input (MBh)625, 800, 812, 988, 1000, 1250, 1375, 1750, 1875, 2500
Nominal output (MBh)500, 640, 650, 790, 800, 1000, 1100, 1400, 1500, 2000
Electric heat
Nominal output (kW)80, 100, 120, 160, 200, 240, 280, 320
Panel filters
Type85% (MERV 13) or 30% (MERV 7 or 8), pleated
Area (sq ft)116.1116.1116.1116.1116.1
Qty–size (in)11–16×20×2, 33–16×25×2
Prefilters (for cartridge filters)
TypePrefilter, 30% (MERV 7 or 8), standard flow
Area (sq ft)64.064.064.064.064.0
Qty–size (in)4–12×24×2, 12–24×24×216–24×24×2
TypePrefilter, 30% (MERV 7 or 8), standard flow
Area (sq ft)80.080.080.080.080.0
Qty–size (in)8–12×24×2, 16–24×24×2
Cartridge filters
Type65% (MERV 11) or 95% (MERV 14), standard flow
Area (sq ft)64.064.064.064.064.0
Qty–size (in)16–24×24×12
Type65% (MERV 11) or 95% (MERV 14), standard flow
Area (sq ft)80.080.080.080.080.0
Qty–size (in)8–12×24×12, 16–24×24×12

NOTE:
1. Gas furnace size availability is limited by minimum airflow (RFS/RPS only).
2. 460-volt capacities are shown. Electric heat availability is limited by minimum airflow (RFS/RPS only).

 

Application Software
Brochures
Case Studies
  • Unit  Moseley Architects Applied Rooftop RoofPak System - Renovation - (1,005KB) (Pub: 2011/06/15)
     
    Models:RPS
     
    The McQuay RoofPak system contributed to building performance at 36.6 percent better than the ASHRAE 90.1 baseline, earning LEED Platinum certification for Moseley Architect’s warehouse. 4 page detailed case study.
  • Unit  Moseley Architects Applied Rooftop RoofPak System - Renovation Project Highlights - (309KB) (Pub: 2011/06/15)
     
    Models:RPS
     
    The McQuay RoofPak system contributed to building performance at 36.6 percent better than the ASHRAE 90.1 baseline, earning LEED Platinum certification for Moseley Architect’s warehouse. 1 page case study brief.
  • Unit  Penn National Gaming Applied RoofPak System - Casino - (7,254KB) (Pub: 2012/12/19)
     
    Models:RPS
     
    The ability to provide savings in energy costs and meet a fast-track construction schedule were critical factors in the selection of Daikin McQuay HVAC equipment for Penn National Gaming's Hollywood Casino in Toledo, Ohio.
Catalogs
Control Integration
Installation and Operation Manuals
Replacement Parts Lists
   Click here to view the Replacement Parts Model Index
  • Unit  Replacement Parts List: 476543 - (1,311KB) (Pub: 2012/08/10)
     
    Models:RBS,RCS,RDS,RFS,RHS,RPS,RWS
     
    RPL: RPS, RFS, RCS, Sizes 018-100, Vintage B / RBS, RDS, RHS, RWS, Sizes 800-808, Vintage B, Applied Rooftop
  • Unit  Replacement Parts List: 552251 - (117KB) (Pub: 2010/09/22)
     
    Models:RPS
     
    RPL: RPS 005-035 Vintage A, Roofpak Heating and Cooling Unit
  • Unit  Replacement Parts List: 552253 - (245KB) (Pub: 2010/09/22)
     
    Models:RPS
     
    RPL: RPS 002-010 Vintage B, Heating and Cooling Unit
  • Unit  Replacement Parts List: 552254 - (305KB) (Pub: 2010/09/22)
     
    Models:RPS
     
    RPL: RPS 012-015 Vintage B, Singlezone Unit
  • Unit  Replacement Parts List: 571177 - (2,996KB) (Pub: 2013/01/17)
     
    Models:RCS,RFS,RPS
     
    RPL: RPS/RFS/RCS, 015-040, Vintage C, Roofpak Applied Rooftop Units
  • Unit  Replacement Parts List: 7000069 - (3,367KB) (Pub: 2012/09/28)
     
    Models:RCS,RDT,RFS,RPS
     
    RPL: RPS, RDT, RFS, RCS, Sizes 045-075, Vintage C, RoofPak Single Zone, Heating and Cooling
  • Unit  Replacement Parts List: 7000070 - (3,473KB) (Pub: 2012/09/28)
     
    Models:RCS,RDT,RFS,RPS
     
    RPL: RCS, RDT, RFS, RPS, Sizes 080-135, RoofPak Single Zone, Heating and Cooling Vintage 'C'
  • Unit  Replacement Parts List: 7000108 - (3,627KB) (Pub: 2012/09/28)
     
    Models:RCS,RDT,RFS,RPS
     
    RPL: RPS, RFS, RDT, RCS Sizes 080-140, Vintage D -Roofpak Single Zone Heating and Cooling
  • Unit  Replacement Parts List: 7000137 - (2,658KB) (Pub: 2012/09/28)
     
    Models:RCS,RDT,RFR,RPS
     
    RPL: RPS, RDT, RFS, RCS 045-079 Tons Vintage D, RoofPak Applied Rooftop Units R410A
  • Unit  Replacement Parts List: 7000150 - (4,101KB) (Pub: 2013/04/26)
     
    Models:RCS,RFR,RPS
     
    RPL: RPS/RFS/RCS, 015-042, Vintage D, Roofpak Applied Rooftop Units
  • Unit  Replacement Parts List: 7000194 - (4,612KB) (Pub: 2013/01/17)
     
    Models:RCE,RDE,RPE
     
    RPL: RPE, RDE, RCE, Sizes 076- 150, RoofPak Evaporative Condenser Vintage C
Revit Templates
Sales and Engineering Data
Seismic Certification